Fire Sprinkler Services by Firecode
Fire Sprinkler Services by Firecode inspects, tests, repairs, and certifies commercial fire sprinkler systems in Manteca, California. The office is at 17964 Ideal Pkwy on the east side of town. Call (209) 753-0981 to schedule an inspection or report a problem with a system.
We work on wet, dry, pre-action, and ESFR sprinkler systems in warehouses, distribution centers, apartment buildings, hotels, schools, medical offices, churches, and retail centers. Most customers are on a quarterly or annual inspection schedule. Others call after a failed fire inspection, a leaking head, or a change in what a building stores.
Inspection and Testing Intervals
Sprinkler systems are inspected and tested to NFPA 25 and California Title 19. Quarterly visits cover the control valves, gauges, water-flow and tamper alarms, and the fire department connection. The annual service adds a walk of the whole building to look at every head, pipe, and hanger, a main drain test, a trip test on dry and pre-action valves, and a flow test where the building has a fire pump. Every five years the system gets an internal pipe inspection and the gauges are replaced or tested. California also requires a five-year certification by a licensed contractor, and we issue the tag and the report that goes with it.
Sprinkler heads have a service life. Standard heads are sample tested at 50 years and quick-response heads at 20 years, then again every 10 years. If a sample fails, the heads of that type are replaced. We check the manufacture dates stamped on the heads during the annual visit and tell you in advance when a test is coming due.
Repairs We Handle
- Leaking, corroded, or painted sprinkler heads
- Heads damaged by forklifts or pallets
- Control valves, check valves, and alarm valves
- Low-point drains and freeze damage on dry systems
- Fire department connections and caps
- Water-flow switches and tamper switches
- Gauges, hangers, and seismic bracing
Call Us When
- Water is dripping from a head or a fitting
- An alarm or trouble signal will not clear
- A control valve has been found closed
- Racking, mezzanines, or stored goods have changed
- A tenant improvement moved walls or ceilings
- The fire department or your insurer asked for a current tag
- The system has not been serviced in over a year
Warehouses and Distribution Centers
Manteca and Lathrop have added millions of square feet of warehouse and distribution space along Highway 99, Highway 120, and Interstate 5. These buildings run on ESFR or large-drop sprinkler systems designed for high-piled storage, and the design only works for the commodity, rack height, and aisle width it was engineered for. Adding a rack level, switching from pallets to plastic totes, or storing aerosols and lithium batteries in a bay designed for cartons can put the building outside its sprinkler design. We review what is being stored against the system’s design criteria and tell you what has to change before the fire marshal or the insurance inspector does.
In-rack sprinklers, flue spaces between pallets, and the 18-inch clearance below ceiling heads are the items written up most often in Manteca warehouses. All three are easy to lose as a building fills up. Our inspection reports call them out by bay and rack row so your warehouse staff can fix them.
Pumps, Backflow, and Standpipes
A sprinkler system is only as good as its water supply. We test fire pumps on the annual flow schedule, test backflow preventers for the City of Manteca and the other water agencies in the county, and inspect standpipes and hose valves in multi-story buildings. One visit can cover all of it.
Fire Extinguishers and Alarms
Most sprinklered buildings also have portable extinguishers and a fire alarm panel that monitors the sprinkler system. We service fire extinguishers on the annual Title 19 schedule and can coordinate fire alarm testing so the water-flow and tamper signals are confirmed at the monitoring company during the sprinkler test.
Service Area
We serve Manteca, Lathrop, Ripon, Escalon, French Camp, and the south side of Stockton, and west to Tracy and Mountain House.
Contact
Fire Sprinkler Services by Firecode
17964 Ideal Pkwy
Manteca, CA 95336
Phone: (209) 753-0981